GDWG-III SF6 Gaaska Diidhiyaha
GDWG-III SF6Baadhaha daadinta gaaska, oo leh tignoolajiyada infrared-ka (NDIR), inta badan waxaa loo isticmaalaa in lagu tilmaamo oo lagu cabbiro daadinta SF6 ee GIS iyo buuxinta qalabka gudaha warshadaha korontada.
Heerka daadinta sanadlaha ee qalabka korantada gaaska SF6 waxaa lagu cabbiraa habka faashadda.Isla mar ahaantaana, qalabka waxaa si weyn loogu isticmaalaa in xafiiska korontada, substations, shirkadda beddelo danab sare, hood shaybaarka iyo imtixaanka sayniska.
●Qalab koronto oo sarreeya
●Helicopter rotor garbaha
●Nidaamka gudbinta gaaska
●Dabdemiska
●Daraasadda heerka hawo-qaadista
●Walxaha halista ah
●Taangiga
●Ma jirto khatar shucaac ah.
●Looma baahna in si joogto ah loo beddelo gaaska argon ee nadiifka ah.
●Looma baahna in si joogto ah loo beddelo dareeraha, kharash-ool ah.
●Looma baahna in la sameeyo jaangooyo toosan sannad kasta, ma jiraan qaybo xidhan.
●Aan ku dhicin huurka, wasakhowga deegaanka ama qulqulka xogta.
●Marka uu jiro dheecaan daran ama SF6xoogga gaasku waa ilaa 100%, ma wasakhayso ama dhaawacmi mayso.
●Si loo cabbiro SF6daadinta gaaska tayo ahaan iyo tiro ahaanba.Xasaasiyadda SF6 gaaska 3g/sanad.
●Si loo helo SF6barta daadinta gaaska.
●Halbeegyada sida SF6xoogga gaaska, heerkulka, qoyaanka, tilmaame koronto, taariikhda iyo heerka bamka diaphragm ayaa la soo bandhigay.
●Interface user-saaxiibtinimo.
●Isticmaal tignoolajiyada NDIR iyo dareemaha horumarsan ee Jarmalka.
●Xawaaraha tijaabada degdega ah iyo ku celcelinta wanaagsan, xogta waxa lagu dejiyaa 10s gudahood.
●Iyada oo heerkulka iyo magdhowga cadaadiska.
●Alaarmiga beenta ah ma jiro, gaas ma jiro marka laga reebo SF6jawaabaha.
●Cabbiraadda gaaska aan lala xidhiidhin waxay hubisaa in dareemaha aanu ku sumoobayn heer kasta oo fiirsashada ah.
●Qolka kulaylka ayaa hubiya in aan heerkulku dhaqaaqin heerkulka dareemaha.
●3.5inch OLED, oo lagu akhriyi karo iftiinka qorraxda ee xoogga badan.
●Ku-dhismay baytari lithium, wakhtiga sugitaanku waa dheer yahay.
●Dhuumaha waxaa loo habeeyey codsi ahaan.
●Muunada nuugista bamka waxay xaqiijisaa xidhidh wanaagsan ee dariiqa gaaska ee tijaabada.
●In ka badan 100 kooxood oo xogta tijaabada ah ayaa lagu kaydiyaa iyadoo lagu saleynayo feejignaanta gaaska iyo waqtiga tijaabada, oo ay fududahay in la weydiiyo.
●Daboolka dibadda ayaa ah xoog sare, si buuxda loo ilaaliyay, qaab dhismeedka walxaha ABS ee aadka u fudud.
●Mabda'a cabbiraadda: Dareemaha infrared aan kala firdhin (NDIR)
●Cabbirka cabbirka: 0-2000ppmv SF6
●Xallinta: 0.1ppmv
●Saxnimada: ± 2% FS
Xataa cabbirka cabbirku wuu ka sarreeyaa 5000ppm, qalabku ma dhaawacmi doono.
●Khaladka ku soo noqnoqda: ≤± 1%
●Dareenka: 1ppmv
●Waqtiga jawaabta: ≤10s
●Waqtiga soo kabashada: ≤15s
●Xasilooni: ≤±20ppm, in ka badan 1000saacadood
●Habka muunadda: Nooca nuugida bamka, socodka ilaa 1L/daqiiqo.
●Bedelka eber: ≤±1% (FS/sanad)
●Cilad toosan: ≤±1%
●Hadda ugu sarreysa: <700mA
●Celceliska awoodda: <2W.
●Cadaadiska hawada ee hawlgalka: 800-1150hPa.
●Qoyaanka deegaanka: 0-95% RH
●Heerkulka kaydinta: -20~+60℃
●Heerkulka shaqada: -20~+50℃
●Qoyaanka hawlgalka: 0-95% (aan-buuxin)
●Korantada shaqaynaysa: 220VAC± 10%,50Hz Ama Ku-dhisan Li-batari, shaqayn joogto ah 6saac ka dib dallaca buuxa.
●Cabirka: 220×250×120mm
●Miisaanka: qiyaastii 2kg
Unugga ugu muhiimsan | 1 set |
Dameeraha | 1 gabal |
Gacanta lagu hayobaadhid | 1 gabal |
Suunka ka-hortagga | 1 gabal |
Hilaa 600mm | 1 gabal |
Isticmaale'hagaha | 1 koobi |
Wkaadhka go'an | 1 koobi |