Tijaabada iska caabbinta dahaarka ee taxanaha GD3128
GD3128 Taxanaha Caymiska Dahaarka Tijaabada wuxuu leeyahay shaqo tijaabo ah oo qumman oo ah cabbirro caabin ah oo kala duwan iyo awood aad u wanaagsan oo ka hortagga faragelinta, kaas oo loo isticmaali karo in lagu tijaabiyo iska caabbinta dahaadhka ee awoodda weyn ee qalabka korantada ee tamarta sare iyo xadhkaha gudbinta ee jawi firfircoon oo xoog leh sida substation.Qalabku wuxuu qaadanayaa shaashadda taabashada midabka dhabta ah, dhammaan xogta tijaabada iyo awoodda batteriga ayaa lagu soo bandhigay isla shaashad isku mid ah marka la eego, isku dhafka furaha iyo furaha ayaa ka dhigaya hawlgalka mid aad u fudud.Isticmaaluhu uma baahna inuu xafido habka hawlgalka.Guji "HELP" shaashadda si aad kor ugu qaaddo habka hawlgalka, kaas oo si wax ku ool ah u hagi kara isticmaalaha inuu ku shaqeeyo qalabka.Qalabku waxa uu leeyahay shaqada qulqulka degdega ah, kaas oo soo saari kara danabka shayga la tijaabiyey isla markiiba iyada oo aan la helin wareeg dheeraad ah oo dareere ah.Qalabka korantada ee qalabka ayaa si toos ah ula socon kara tamarta nool ee shayga la tijaabiyay.Haddii danabku dhaafo 36V, tijaabada si toos ah ayaa loo mamnuuci doonaa, taasoo si wax ku ool ah u ilaalin karta qalabka iyo hawl-wadeenada.
Qalabku waxa uu qaadanayaa baakidh lithium ah oo awood weyn lagu soo dallaci karo.Saacadaha tijaabada qalabku waxa uu si toos ah u diiwaangeliyaa wakhtiga tijaabada waxaanu ku kaydiyaa natiijada imtixaanka taariikhda iyo wakhtiga.Shaashadda taabashada waxay si fudud u heli kartaa xogta taariikhiga ah ee la duubay.Isku xirka USB-ga ee gebi ahaanba go'doonsan wuxuu si badbaado leh ugu shubi karaa xogta tijaabada kombayutarka.Qalabku waxa uu ku qalabaysan yahay xariiq tijaabo ah oo leh dahaar laba-laab ah iyo lakabka gaashaanka, iyo bar danabeedka sare waxa lagu rakibay qalab algator ah oo la bedeli karo iyo jillaab, kaas oo la qabsan kara meelo kala duwan oo tijaabo ah.Qalabku wuxuu qaataa qaab-dhismeedka qolof-lakab adag oo adag, iyo heerka ilaalinta ee sanduuqa dibadda waa IP65, kaas oo ka hortagi kara duulaanka qoyaanka iyo boodhka inta lagu jiro gaadiidka iyo kaydinta, oo si wax ku ool ah uga ilaaliyo qalabka isku dhaca.
Taxanaha GD3128 wuxuu leeyahay baaxad ballaaran, xallin sare, hawlgal ku habboon, adkeysi iyo adkeysi, saxnaanta iyo isku halaynta, waxqabadka xasilloon, iyo awood xoog leh oo ka hortagga faragelinta.Qalabku wuxuu leeyahay tijaabada caabbinta dahaarka (IR);Tijaabada index polarization (PI);tijaabada saamiga nuugista (DAR);Imtixaanka ramp (RAMP);tijaabada filter (FR, 10S, 20S, 30S, 40S afar doorasho);tijaabada danab (V);tijaabada awoodda (uF);imtixaanka hadda (nA) iyo hawlo kale.Qalabku wuxuu ku habboon yahay tijaabada caabbinta xakamaynta ee qalabka korantada, xadhkaha gudbinta iyo qalabyada kale ee waaweyn ee hoos yimaada deegaanka awoodda weyn, koronta sare iyo soo-gelinta xooggan.Waa qalab caadi ahaan loo isticmaalo oo aan looga maarmin korontada, isgaarsiinta, saadaasha hawada, qolka kombayuutarka, goobta saliidda, rakibaadda iyo dayactirka qalabka korontada, iyo waaxaha korontada ee warshadaha iyo macdanta.
●Xilliga ugu badan ee wareegga gaaban waa 7mA.
●Tijaabada iska caabinta dahaarka (IR), tijaabada index polarization (PI), tijaabada saamiga nuugista (DAR).
●Habka tijaabada Ramp (RAMP), qaabka tijaabada filter (FR), tijaabada awooda (uF)
●Shaqada kormeeraha korantada, si toos ah ula soco tamarta la dallacay ee shayga la tijaabiyay.
●Tijaabi shaqada saacadeeyaha, si toos ah u duub wakhtiga tijaabada.
●Si toos ah u shaqaynaysa, si toos ah oo degdeg ah u sii daaya kharashka shayga tijaabada ka dib tijaabada, iyada oo aan lahayn wareegga dareeraha dibadda.
●Shaqada daminta tooska ah
●Shaashada midabka taabashada weyn.
●Qaab dhismeedka qolof-lakabka ah, adag oo waara, heerka ilaalinta IP65.
●Xirmada baytariyada lithium ee awoodda sare leh dib loo dallaci karo.
●Shaqada kaydinta, waxay si toos ah u kaydin kartaa 1000 kooxood oo ah xogta imtixaanka wakhtiga-dhabta ah oo leh taariikhda iyo wakhtiga iyo wakhtiga tijaabada.
●Soo dejinta, oo ku qalabaysan interface USB, xogta diiwaanka waxaa lagu dhejin karaa kombuyuutar si loo baaro xogta xogta.
Qaabka Alaabta | Voltage lagu qiimeeyay | Range Resistance Insulation | Wareegga Gaaban ee Hadda |
GD3128A | 250V,500V,1kV,2.5kV,5kV | 0.50MΩ~10.0TΩ | ≥7mA |
GD3128B | 250V,500V,1kV,2.5kV,5kV,10kV | 0.50MΩ~20.0TΩ | ≥7mA |
GD3128C | 250V,500V,1kV,2.5kV,5kV,10kV,15kV | 0.50MΩ~30.0TΩ | ≥7mA |
Qiyaasta iska caabinta dahaarka iyo saxnaanta
Voltage lagu qiimeeyay | Xanaaqa iska caabinta dahaarka | Saxnaanta | Odhaah |
250V | 0.50MΩ~50.0GΩ | ±5%rdg±3dgt |
|
50.0GΩ~500GΩ | ±20%rdg±3dgt |
| |
500V | 1.00MΩ~100GΩ | ±5%rdg±3dgt |
|
100GΩ~1.00TΩ | ±20%rdg±3dgt |
| |
1000V | 1.00MΩ~200GΩ | ±5%rdg±3dgt |
|
200GΩ~2.00TΩ | ±20%rdg±3dgt |
| |
2500V | 1.00MΩ~500GΩ | ±5%rdg±3dgt |
|
500GΩ~3.00TΩ | ±20%rdg±3dgt |
| |
5000V | 1.00MΩ~1.00TΩ | ±5%rdg±3dgt |
|
1.00TΩ~10.0TΩ | ±20%rdg±3dgt |
| |
10KV | 1.00MΩ~2.00TΩ | ±5%rdg±3dgt |
|
2.00TΩ~20.0TΩ | ±20%rdg±3dgt |
| |
15KV | 1.00MΩ~3.00TΩ | ±5%rdg±3dgt |
|
3.00TΩ~30.0TΩ | ±20%rdg±3dgt |
1 TΩ (Tera ohm)=1000GΩ=1012Ω
1 GΩ (Giga ohm)=1000MΩ=109Ω
1 MΩ (Mega ohm)=1000KΩ=106Ω
Shaqada | Cabbirka caabbinta dahaarka (IR);Qiyaasta tusmada polarization (PI);saamiga nuugista (DAR);Habka tijaabada ramp (RAMP);filtershaqayn(10S, 20S, 30S, 40S);vcabbirka oltage (V);capacitaansicabbirid(uF);cabbirka hadda(nA) |
Bixinta Korontada | Batari lithium ah oo dib loo soo celin karo 6.2Ah |
Voltage lagu qiimeeyay | GD3128A: 250V, 500V, 1kV, 2.5kV, 5kV GD3128B: 250V, 500V, 1kV, 2.5kV, 5kV, 10kV GD3128C: 250V, 500V, 1kV, 2.5kV, 5kV, 10kV, 15kV |
Saxnaanta Voltage-ka soo-saarka | (5%~10%) ±10V |
Xaddiga Tijaabada Iska-caabbinta Dahaarka | GD3128: 0.50MΩ~10.0TΩ GD3128B: 0.50MΩ~20.0TΩ GD3128C: 0.50MΩ~30.0TΩ |
Soo saarida Wareegga Gaaban ee Hadda | ≥7mA |
Tijaabada Tusmada Polarization | Haa |
Tijaabada saamiga nuugista | Haa |
Habka Imtixaanka Ramp | Ku tijaabi tillaabooyinka 10% ee danabkii hore loo dhigay ilaa korantada la sii dajiyay. |
Qaabka Tijaabada Shaandhee | 10S, 20S, 30S, 40S afar doorasho. |
Tijaabada Korantada | Range: AC/DC: 0V~1000V; Saxnimada: ± 5%rdg± 3V |
Imtixaanka Awoodda | Range: 10nF~25uF; Saxnimada: ± 10%rdg ± 10nF |
Imtixaanka hadda | Range: 0.01nA~7mA; Saxnimada: ± 5%rdg±0.5nA |
Kormeeraha Korantada | La soco korontadaxiniinyahad shayga, oo la socda heerka dheecaanka tijaabada ka dib, mamnuuc in la tijaabiyo marka danabku dhaafo 36V, ilaali qalabka iyo hawlwadeenka. |
Tijaabada Saacadaha | Waqtiga tijaabada duubista tooska ah, timingkala duwan: 0s ~ 9999s |
Shaqada Kaydinta | Si toos ah u kaydi xogta imtixaanka taariikhda iyo wakhtiga imtixaanka, wadarta 1000 kooxood |
Shaqada soo dejinta | U soo rar xogta kaydsan kombayutarka adigoo isticmaalaya fiilada isgaarsiinta USB. |
Muujinta Awoodda baytariga | Muujinta awoodda batteriga, marka korantada batarigu hooseeyo waxay xasuusin doontaalacagbatteriga. |
Daminta tooska ah | 15 daqiiqo ka dib bilawga si toos ah ayuu u xidhmi doonaa iyada oo aan wax qaliin ah la samayn. |
Cabirka | 280mm×260mm×160mm |
Miisaanka | 4900g (ku dar batteriga) |
Tijaabi fiilooyinka | Midabka cas ee tijaabada koronta sare ee siliga 1pc (oo leha kilibka alligator iyo jillaab), siliga tijaabada midabka cagaaran 1pc, siliga tijaabada midabka madow 1pc |
Heerka Ilaalinta | Xidh kiiska IP65, fur furaha IP40 |
Deegaanka shaqada | -20℃~50℃; 80% rh |
Bakhaarka Deegaanka | -25 ℃~65℃; 80% rh |
Iska caabinta dahaarka | 50MΩ(1000V) (inta u dhaxaysa wareegga tijaabada iyo qolofka) |
U adkeysan Voltage | AC 3kV50Hz 1 daqiiqo(inta u dhaxaysa wareegga tijaabada iyo qolofka) |
Badbaadada | IEC61010-1, IEC61326-1 |