GDSF-311WPD 3-In-1 SF6 Falanqeeyaha Gaaska
GDSF-311WPD (GDSF-411WPD) waa qalab ku haboon marka ay lagama maarmaan tahay in la tijaabiyo waxa ku jira biyaha, daahirsanaanta iyo burburka gaaska SF6.Xudunta u ah tijaabada dhibicda sayaxa waa dareemayaasha taxanaha DRYCAP® oo ay soo saartay shirkadda Finland Vaisala.Mabda'a infrared-ka ee SF6 gaaska tijaabinta nadiifinta gaaska ay soo saartay Shirkadda Dareemaha Yurub waxaa loo isticmaalaa in lagu tijaabiyo nadiifnimada gaaska SF6.Dareemaha elektiroonigga ah ee ay soo saartay Shirkadda Mombabo ee Switzerland waxa loo isticmaalaa sidii cunsur dareeneed ee tijaabinta alaabta burburka gaasta SF6.Iyada oo leh chips hardware-ka xirfadlayaasha ah iyo algorithms-yada software ee STMicroelectronics, waxaan soo saarnay jiil cusub oo ah 3-in-1 gaas falanqeeye.
SF6Qoyaanka
●Habka cabbirka: Mabda'a cabbiraadda adkaysiga iyo awoodda
●Baaxadda cabbirka: barta sayaxa -80℃--+20℃(taageerada ppmv)
●Saxnimada: ± 1℃
(marka heerkulka barta sayaxa uu ka hooseeyo 0 ℃, wax soo saarka dareemayaasha waa barta dhaxan)
●Waqtiga jawaabta: 63% [90%]
+20→-20℃ Td 5s[45s]
-20→-60℃ Td 10s[240s]
●Xallinta: 0.01℃
●Ku celcelinta: ± 0.5 ℃
●Cutubka muujinta: ℃, ppm, ℃P20(qiimaha loo beddelay 20℃)
●Qulqulka gaaska: 400-600ml/min
●Muujinta socodka: 0-1000mL mitir socodka dhijitaalka ah
●Tusaalaha cadaadiska gaaska: ≤1MPa
SF6daahirnimo
●Habka cabbiraadda: Mabda'a Cabbirka Infrared (Dareemaha taxanaha NDIR)
●Qiyaasta kala duwan: 0 ~ 100% SF6
●Waqtiga jawaabta: [90%] 60s
●Saxnimada: ± 0.5%FS
●Ku celcelinta: ± 0.5%
●Xallinta: 0.01%
●Unugga bandhiga: %
SF6Alaabta Burbursan
●Habka cabbiraadda: Mabda'a Cabbiraadaha Korantada (Electrochemical Measurements)
●Cabbirka cabbirka: H2S: 0 ~ 200ppmv
SO2: 0 ~ 200ppmv
CO: 0 ~ 500ppmv
HF: 0 ~ 50ppmv
●Saxnimada: H2S: 10ppmv ± 3%
SO2: 10ppmv ± 3%
CO: 50ppmv ± 4%
HF: 10ppmv ± 3%
●Ku celcelinta: H2S: 10ppmv ± 2%
SO2: 10ppmv ± 2%
CO: 50ppmv ± 2%
HF: 10ppmv ± 2%
●Xallinta: 0.01ppmv
●Unugga bandhiga: ppmv
●Korontada: 220VAC± 10%, 50Hz, isticmaalka AC/DC, ilaalinta xad-dhaafka ah, shaqada joogtada ah kama hoosayso 8hours.
●Isticmaal heerkulka deegaanka: -20--+60 ℃
●Qoyaanka deegaanka: 90% RH
●Saamaynta qiimaha cabbirka: Wax saamayn ah oo cadaadiska iyo socodka ah ma laha
●Cabirka: 395*295*155mm
●Miisaanka: qiyaastii 2kg.
GDSF-411WPD SF6Alaabta Burbursan
●Saxsanaanta: H2S: <10ppmv ±0.3ppmv;> 10ppmv ± 3%
SO2: <10ppmv ± 0.3PPmv;> 10ppmv ± 3%
●Ku celcelinta: H2S: <10ppmv ±0.2ppmv;> 10ppmv ± 2%
SO2: <10ppmv ± 0.2PPmv;> 10ppmv ± 2%
●Shaqada dib u warshadaynta iyo buuxinta: qolka dib u warshadaynta 2L,waqtiga dib u warshadaynta ≤ 5 daqiiqo
Iyadoo shaqaynaysa qalajinta gaaska
●Cabirka: 395*295*315mm
●Miisaanka: qiyaastii 5kg.
Tijaabada ugu weyn | 1 gabal |
Adapter | 1 dhigay |
Dhuumaha Teflon (oo ay ku jiraan waalka hagaajinta socodka iyo xiriiriyaha degdega ah) | 1 dhigay |
Dhuumaha dabada | 1 dhigay |
Qaybaha tafaariiqda | 1 dhigay |
Dameeraha | 1 gabal |
Isticmaale's Hagaha | 1 gabal |
Warbixinta Imtixaanka | 1 gabal |