Tijaabada Saliidda Dahaarka ee GDOT-80A
●Fadlan si taxadar leh u akhri buug-gacmeedka hawlgalka ka hor inta aanad shaqayn.
●Fadlan hubi in tijaabiyaha uu si fiican ugu xiran yahay dhulka ka hor inta aadan tijaabin.
●Waa mamnuuc in la dhaqaajiyo ama kor loo qaado daboolka tijaabada inta lagu jiro habka tijaabada si looga fogaado dhaawaca koronta sare.Korontadu waa in ay dansataa ka hor inta aan la bedelin saliidda muunada.
●Si taxadar leh ula tacaal markaad iska bixinayso ama xidhayso daboolka tijaabada tamarta sare!
●Haddii tijaabiyaha uu u shaqeeyo si aan caadi ahayn ka dib marka saliidda dahaadhka ahi ay jabto, fadlan dami tijaabiyaha ilaa 10 ilbiriqsi, ka dibna dib u bilow.
●Ka dib markii warqadda daabacadu dhammaato, fadlan tixraac qaybta sharraxaadda daabacaha (ama lifaaqa gacanta) si aad u beddesho warqadda daabacaadda si aad uga fogaato dhaawaca madaxa daabacaha.
●Tijaabiyaha ka fogee qoyaanka, boodhka iyo walxaha kale ee daxalka, kana fogee ilaha heerkulka sare.
●Si taxadar leh ula dhaqan gaadiidka.Hoos ha u dhigin.
●Buuggu waxa uu dib u eegi karaa si waafaqsan ogeysiis dheeraad ah oo hore.Haddii wax su'aal ah, fadlan nala soo xiriir.
Muddada dammaanadda ee taxanahan waa hal sano laga bilaabo taariikhda shixnadda.Fadlan tixraac qaansheegtaada ama dukumeentiyada rarida si aad u go'aamiso taariikhaha dammaanadda ee habboon.Shirkadda HVHIPOT waxay dammaanad qaadaysaa iibsadaha asalka ah in alaabtani ay ka xoroobi doonto cilladaha alaabta iyo shaqada ee isticmaalka caadiga ah.Inta lagu jiro muddada dammaanadda, bixi in cilladaha noocan oo kale ah aysan go'aamin HVHIPOT inay ka dhasheen xadgudub, si xun u isticmaal, beddelaad, rakibid aan habboonayn, dayacaad ama xaalad deegaan oo xun, HVHIPOT waxay ku xaddidan tahay oo keliya hagaajinta ama beddelka qalabkan inta lagu jiro muddada dammaanadda.
Qalabka GDOT-80C | 1 pc |
Koob saliid (250ml) | 1 pcs |
Xadhiga korantada | 1 pc |
Fiyuuska kaydka ah | 2 pcs |
Usha walaaqaya | 2 pcs |
Qiyaasta caadiga ah (25mm) | 1 pc |
Warqad daabac | 2 duub |
Tweezer | 1 pc |
Tilmaamaha isticmaalaha | 1 pc |
Warbixinta tijaabada warshadda | 1 pc |
HV Hipot Electric Co., Ltd. ayaa si adag oo taxadar leh u akhriyay buug-gacmeedka, laakiin ma dammaanad qaadi karno in aanay jirin wax khalad ah iyo khaladaad gebi ahaanba ku jira buug-gacmeedka.
HV Hipot Electric Co., Ltd. waxaa ka go'an in ay si joogto ah u horumariso hawlaha alaabta, iyo hagaajinta tayada adeegga, sidaas darteed shirkadu waxay weli xaq u leedahay inay beddesho wax kasta oo badeecooyin ah iyo barnaamijyada software ee lagu sharraxay buug-gacmeedkan iyo sidoo kale nuxurka buug-gacmeedkan iyada oo aan horay loo arag. ogeysiis.
Xakamaynta gudaha ee qalab koronto oo badan oo ku jira nidaamyada korantada, nidaamyada tareenada, dhirta batroolka ee waaweyn iyo shirkadaha, ayaa inta badan la qaatay nooca dahaarka saliidda ka buuxo, sidaas darteed, tijaabinta xoogga saliidda ee saliidda waa mid caadi ah oo lagama maarmaan ah.Si loo daboolo baahiyaha suuqa, waxaanu soo saarnay oo aanu soo saarnay taxane ah oo ah tijaabiyeyaal awood-dielectric saliid ah oo dahaaran iyadoo loo eegayo heerka qaranka GB/T507-2002, heerka warshadaha DL429.9-91 iyo Heerka Warshadaha Awooda Korontada ee ugu dambeeyay DL/T846.7 -2004 nafteena.Qalabkan, adoo isticmaalaya microcomputer hal-chip ah oo udub dhexaad u ah, waxay xaqiiqsadeen hawlgal toos ah, cabbir sax ah oo sarreeya, si weyn u hagaajinaya waxtarka shaqada iyo yaraynta xoogga shaqada ee shaqaalaha.Waxaa intaa dheer, waa mid yar oo cabbir ah oo ku habboon in la qaado.
●Iyada oo microprocessor, si toos ah u buuxi tijaabada korantada adkeysiga ee wareegga saliidda oo leh 0 ~ 80KV (oo ay ku jiraan kor u qaadista, ilaalinta, isku dhafka, istaagida, xisaabinta, daabacaadda iyo hawlgallada kale).
●Shaashad weyn oo LCD ah.
●Hawlgal fudud.Mashiinku wuxuu si otomaatig ah u dhammaystiri doonaa tijaabada korantada ee hal koob oo saliid muunad ah ka dib marka uu dejiyo hawlwadeenku.Qiimaha korantada ee 1 ~ 6 jeer iyo wakhtiyada wareegyada si toos ah ayaa loo keydin doonaa.Imtixaanka ka dib, daabacaha kulaylka ayaa daabici doona qiimaha danab kasta oo burburay iyo celceliska qiimaha.
●Ilaalinta awoodda hoos u dhigista.Waa awoodbadbaadi 100 natiijooyin tijaabo ah oo muuji heerkulka hadda jira iyo huurka.
●Qabo kombuyuutar hal-chip ah si aad kor ugu qaaddo xawaaraha joogtada ah.Inta jeer ee danabku waa sax at 50HZ, hubi in habka oo dhan ay fududahay in la xakameeyo.
●Iyada oo koronto-badan, hadda-badan iyo ilaalinta xaddidan si loo hubiyo badbaadada hawl-wadeennada.
●Iyada oo shaqada muujinaysa heerkulka la qiyaasay iyo saacadda nidaamka.
●Kumbiyuutarka kula xidhiidh interface RS232 caadiga ah.
Korontada | AC220V± 10%, 50Hz |
Korontada wax soo saarka | 0~80kV(La dooran karo) |
Awood | 1.5kVA |
Awood | 200W |
Xawaaraha korontadu | 2.0~3.5kV/s (la hagaajin karo) |
Voltagecabbiriddasaxnaanta | ± 3% |
Waveform qalloocan | ≤3% |
Kordhinta muddada | 5 daqiiqo (La hagaajin karo) |
Waqtiga taagan | 15 daqiiqo (La hagaajin karo) |
Waqtiyada kobcinta | 1~6 (La dooran karo) |
Hawlgalkadeegaanka | Temperature: 0℃-45℃ |
Hxudunta:Max.qoyaan qaraabo75% | |
Cabirka | 465x385x425mm |