GDQH-601-50 SF6 Gaaska Dib u warshadaynta
Qalabka beddelka SF6, faakiyuumka gaaska GIS iyo cabbiraadda.
Nadiifinta qalabka laftiisa iyo cabbirka.
Buuxinta gaasta ee beddelka SF6.
Dib u warshadaynta gaaska SF6 ee qalabka korontada.
Qalaji SF6 gaaska dib u warshadaynta ama buuxinta.
Haanta kaydinta oo ka kooban mug 50L.
Si fudud loo dhaqaajin karo
- Bamka faaruqinta: Leybold D16C, 16m3/H@50Hz
- Compressor: GDQH-301H 6.75m3/H
- Habka qaboojinta: Cutub hawo qaboojiyey
- Haanta kaydinta 50L weel, 3.6MPa
- Valve: kubad-valve 3-365R01 DN20
- Nidaamka xakamaynta: Waxay samayn kartaa hawlgallo kala duwan iyo la socodka qalabka qalabka.
- Tuubada isku xirka: DN10 Tuubada cadaadiska sare ee M20 * 1.5
- Heerka faaruqinta: 16M3/H (ugu badnaan 25M3/H), Shahaadada Vacuum: 10Pa
- Sicir bararka: 10M3/ H (cadaadiska dhuumaha waa 1.6Mpa)
- Heerka soo kabashada: 6.75M3/H (gaaska dib u warshadaynta)
- Heerka soo kabashada SF6: ka sarreeya 95-98%.
- Heerkulka deegaanka shaqada: -10℃~+45℃
- Haanta Kaydka: 50L, 3.6MPa.
- Cadaadiska hore ee soo kabashada: 8bar.
- Korontada: 220V± 10%, 50/60Hz.
- Awoodda: 4kW.
SF6 mashiinka dib u warshadaynta gaaska *1
Xadhkaha korontada *1
Tuubada Xidhiidhka Cadaadiska Sare *3
O-ring *wax yar
Tilmaamaha isticmaalaha *1
Warbixinta tijaabada warshada *1