GDBT-8610P Tijaabada Xakamaynta baytariga
GDBT-8610P Tester Battery ayaa si weyn loogu isticmaalaa meelaha soo socda:
●Telecom: Xafiiska Dhexe, xarumaha xogta iyo goobaha fogfog
●Utility Power: Qalabka Bedelka, Saldhigga Korontada iyo Warshada Korontada
●Macaahidda Maaliyadeed: Xarumaha Xogta Shirkadaha
●Petrochemical: Nidaamyada xakamaynta habka
●Meelaha xeebaha ka baxsan
●Dawlad: Deegaan iyo Gobol
●Xarumaha Hagaajinta Cashuuraha iyo Dakhliga
●Homeland Security, Schools, Army and Marine
●Xarumaha Ciidanka Cirka, Dabdamiska iyo Hay'adaha Booliiska
●Nidaamka UPS ee isbitaalka
●Alaab-qeybiyeyaasha baabuurta korontada
●Sawirada batteriga SLA
●Tijaabada ballaaran: 5 ~ 6000Ah, ku habboon hal unug oo ah 1.2V, 2V, 6V iyo 12V
●Qalabka gacanta lagu hayo ee caqli badan oo la qaadan karo, qalafsan oo si fudud loo socon karo
●Shaashada taabashada midabka leh oo leh hawlo ikhtiyaari ah oo kiiboodhka ah
●Isla mar tijaabi korantada, caabbinta iyo qiyaasta awoodda baytariyada
● Cabbirka khadka tooska ah, looma baahna in laga saaro batteriga iyo xadhigga nidaamkiisa si loo tijaabiyo, badbaado leh oo habboon
●Tijaabada degdega ah ee batteriga iyo xadhkaha ilbidhiqsiyo gudahood iyadoo la tijaabinayo xogta kaydinta
● Faragelinta xooggan ee ka-hortagga wakhtigan sare leh oo leh hawl-qabad deggan oo sax ah
●Tijaabinta inta jeer ee ka hooseysa 10 Hz, si wax ku ool ah uga fogow faragelinta iska caabinta awoodda batteriga lafteeda
●Ku toos USB Drive-ka cusboonaysiinta software-ka iyo ku wareejinta xogta PC si aad u sii baarto
●Kombuyuutar maamul oo awood badan, oo ku habboon kaydinta xogta iyo falanqaynta
●Xusuus weyn oo lagu baadho kaydinta xogta in ka badan 3000 unug
●Shaqada qaylo-dhaanta qaylo-dhaanta iyo ilaalinta korantada oo ka badan, ammaan ah in la isticmaalo
●Si toos ah u shaqaynaysa tijaabada ka hor, iyada oo kor u qaadeysa saxnaanta tijaabada
●Dib u tijaabinta iyo shaqada magdhowga: qalitaan kasta oo khalad ah ama la dhaafo waxaa dib loogu tijaabin karaa si fudud hal mar
●Xogta tixraaca gudaha xusuusta ee isbarbardhigga imtixaankaaga, iyo qiimayaal tixraac is-qeexay ayaa diyaar ah
Baaxadda iska caabinta | 0.00mΩ ~ 100mΩ | Kala duwanaanshaha korantada | 0.000V ~ 16V* |
Xallinta tijaabada min-voltage -iska caabin
| 1mv 0-999μΩ: 1 μΩ 1-9mΩ: 10μΩ(0.01mΩ) 10-99mΩ: 100 μΩ (0.1mΩ) | Tijaabi saxnaanta -voltage - iska caabin
| ± 0.2%rdg ± 6dgt 0μΩ-250μΩ: 8% ± 6DGT 250μΩ-500μΩ: 3% ± 6DGT 500μΩ-100mΩ: 1%± 6DGT |
Korontada | 7.2V 2400mAhBateriga Li-ion | Waqtiga shaqada | In ka badan 5 saacadood ka dib dalaci buuxa |
Cabbiraadda xusuusta xogta | 3000 unug | Deegaanka hawlgalka | 0 ℃ ilaa 40 ℃90% RH |
Bandhig LCD | 320*240 pixel TFT shaashadda taabashada | Cabirka(cutubka ugu muhiimsan) | L210*W110*H60 mm |
Miisaanka saafiga ah(xirmo) | 2 kg | Com dekedda | Mini USB |