Bishii Agoosto, farsamayaqaannada iibka ka dib ee HV Hipot waxay aadeen Xiangyang.Ujeedada safarkani waxay ahayd in la bixiyo adeegyada kaxaynta korantada ee shirkadda Xiangyang Power Supply Company.
Ka dib markaad timaaddo goobta, iyadoo la kaashanayo iyo iskaashiga macaamilka, rakibidda koronto-dhaliyaha danabka hillaaca ayaa la fulin doonaa.
Qalabaynta goobta ee GDCY-400kV koronto dhaliyaha danabka
Qiyaasida fogaanta kubbadda goobta: cabbirida masaafada kubbadda jidhka iyo cabbirida masaafada kubbadda gooysa (3000/200/la qiyaasay)
Tijaabada ku-socodka goobta: 30KV imtixaanno badan oo togan iyo taban (la kulan T1=1.2±30%/T2=50±20%us/TC=2 ilaa 6us)
Tijaabada xoogga goobta: danab lagu qiimeeyay 80% wax soo saarka
Tababarka aragtida iyo hawlgelinta goobta:
Ku-dhaqanka macmiilka – tijaabada alaabta tijaabada ah ee la mid ah: 10KV koronto-baddeliye
1. Tijaabada mawjada buuxda
Shuruudaha tijaabada: tijaabinta danab 75KV, wakhtiga waveform T1=1.2±30%/T2=50±20% us
Hawlgalka goobta: iyadoo la adeegsanayo wax soo saarka danab laba-heer ah
Hababka mowjada goobta:
Mawjada madaxa iska caabbinta: 150Ω heerka koowaad, 500Ω heerka labaad (2 1KΩ barbar socda)
Iska caabin dabada hir: heerka 1aad 45Ω, heerka 2aad 45Ω
Tijaabi hawlgalka iyo qaabka mawjada:
2. Tijaabada goynta
Shuruudaha tijaabada: tijaabinta danab 85KV, wakhtiga madaxa mawjada T1 = 1.2 ± 30%, wakhtiga goynta TC=2 ilaa 6us
Hawlgalka goobta: iyadoo la adeegsanayo wax soo saarka danab laba-heer ah
Hababka mowjada goobta:
Iska caabbinta mawjada madaxa: Heerka 1 75Ω, Heerka 2 500Ω (2 1KΩ barbar socda)
Iska caabin dabada hir: heerka 1aad 45Ω, heerka 2aad 45Ω
Tijaabi hawlgalka iyo qaabka mawjada:
Tababarkan taxanaha ah ka dib, macaamiishu waxay si qoto dheer u fahmaan dhammaan qalabka qalabka, taas oo ka dhigaysa macaamilka inuu ku kalsoon yahay hawlgalka dhabta ah!