GDCR3000B Digital Resistance Tester
GDCR3000B Iska caabbinta Dhulka/Tijaabada Carrada ayaa si gaar ah loogu talagalay in lagu cabbiro caabbinta dhulka, iska caabbinta ciidda, danabka dhulka iyo danab AC.Farsamadii ugu dambeysay ee dhijitaalka ah iyo kuwa yar yar ayaa la qaatay, si loo cabbiro caabbinta dhulka 4-tiir, 3-tiir ama 2-tiir.FFT (Fourier transform) tignoolajiyada, tignoolajiyada AFC (xakamaynta soo noqnoqda tooska ah) sidoo kale waa la heli karaa, oo leh awood wanaagsan oo ka hortagga faragelinta iyo awooda la qabsiga deegaanka, si loo hubiyo saxnaanta sare, xasilloonida sare iyo isku halaynta.Waxaa si weyn loogu isticmaalaa cabbiraadda awoodda korontada, isgaarsiinta, saadaasha hawada, goobta saliidda, dhismaha, ilaalinta iftiinka, qalabka korontada warshadaha.
GDCR3000B waxay ka kooban tahay mashiinka martida loo yahay, software kormeerka, fiilooyinka tijaabinta, usha dhulka kaaliyaha ah, fiilada isgaarsiinta iyo kuwa kale.Bandhigga weyn ee LCD ee mashiinka martida loo yahay ayaa leh nalka dambe ee buluugga ah iyo garaafyada bar oo muujinaya in si cad loo arki karo.Isla mar ahaantaana waxay kaydin kartaa 300 oo xog ah, waxay xaqiijin kartaa su'aal taariikhi ah iyo hawlaha kormeerka waqtiga dhabta ah ee internetka iyada oo loo marayo kormeerka software, bandhig firfircoon, calaamad muujinaysa, oo leh hawlaha akhriska, dib u eegista, kaydinta, warbixinta iyo daabacaadda xogta taariikhiga ah.
1. Heerka Heerka iyo Xaaladda Shaqada
Xaaladda caadiga ah | Xaalada Shaqada | Odhaah | |
heerkulka deegaanka | 23℃±1℃ | -10℃~40℃ | ---- |
Qoyaanka deegaanka | 40%~60% | <80% | ---- |
Voltage shaqeeya | 9V±0.1V | 9V±1.5V | ---- |
Caabinta Dhulka Kaaliyaha | <100Ω | <30kΩ | rC,rP |
danab faragelin | ---- | <20V | ---- |
Faragelinta hadda | ---- | <2A | ---- |
Masaafada korantada ee tijaabada R | a>5d | a>5d | ---- |
Fogaanta korantada eeρimtixaan | a>20h | a>20h | ---- |
2. Tilmaamaha Guud
Hawlaha | 2-cir / 3-cir / 4-cirCabbirka caabbinta dhulka,iska caabin ciidda,danab dhulka, koronto ACcabbirid. |
Bixinta Korontada | DC 9V(Zn-Mn baytari qallalan R14S 1.5V 6 xabo,Sii socotawakhtiga sugitaanka300saac) |
Range | Iska caabinta Dhulka: 0.00Ω~30.00kΩ |
Iska caabbinta ciidda: 0.00Ωm~9000kΩm | |
Danab dhulka: 0V-600V | |
Nooca cabbirka | 4-cir,3-cir, 2-tiir caabbinta dhulka cabbirka. |
Hababka Qiyaasta | Iska caabinta dhulka: Habka beddelka tiirka hadda la qiimeeyay.Tijaabi curent Max.20mA Iska caabbinta ciidda: Habka 4 tiir (Habka Wenner). Voltage Earth: Celceliska rectifier[P(S)-ES dekedda] |
Inta jeer ee tijaabada | 128Hz/111Hz/105Hz/94Hz(AFC) |
Imtixaanka Wareegga Gaaban ee Hadda | AC 20mA max |
Furitaanka Korantada Imtixaanka Wareegga | AC 40V ugu badnaan |
Tijaabi qaabka Voltage Waveform | Sine Wave |
Kala fogaanshaha Electrodes Fogaanta | waa la dejin karaa1m-100m |
Bedelka Heerka | Iska caabinta Dhulka: 0.00Ω-30.00kΩ Shidaal otomaatig ahing. |
Iska caabbinta ciidda: 0.00Ωm-9000kΩm otomaatig ahing. | |
Iftiin danbe | Iftiinka dambe ee shaashadda buluugga ah |
Qaabka Muujinta | 4 muuqaal LCD digital ah, Iftiinka dambe ee shaashadda buluugga ah |
Iftiinka Tilmaamaha | Iftiishka tusiyaha LED inta lagu jiro tijaabada, Muujinta hoos u tirinta LCD |
Cabirka LCD | 128mm*75mm |
Muujinta LCD | 124mm*67mm |
Cabirka | 215mm*190mm*95mm |
Hormoodka Imtixaanka caadiga ah | Wadarta 4 hoggaan: 1* Casaan20m, 1* Madow20m, 1* Jaalle10m, 1*Cagaar10m |
Hogaaminta Imtixaanka Fudud | 2 horseed: 1* Casaan 1.6m,1*Madaw 1.6m |
Kaaliyaha Ground Electrodes | 4 qaybood:φ10mm×150mm |
Waqtiga Qiyaasta | Kuleylka dhulka: qiyaastii 3 jeer/sek |
Iska caabinta dhulka, iska caabin ciidda: qiyaastii 5 sekan/wakhti | |
Waqtiyada Qiyaasta | In ka badan 5000 jeer (imtixaanka wareegga gaaban, tijaabi 1 jeer, jooji 30 ilbiriqsi ka dib si aad u tijaabiso) |
Korantada Wareegga | Si loo tijaabiyo ka hooseeya AC 600V |
Dekadda isgaarsiinta | Interface USB, xogta la xafiday ayaa lagu shubi karaa PC si loo kaydiyo loona daabaco. |
Hogaanka Isgaarsiinta | USB,1.5m * 1 xabbo |
Kaydinta Xogta | 300 koox,"MEM”kaydinta tilmaame,"BUUXA”astaan muujinaysa in kaydintu buuxdo |
Hayso Xogta | Shaqada haysashada xogta: "HOLD" bandhigay icon |
Xogta Akhri | Shaqada akhriska xogta: "AKHRISO" muujinta summada |
Muujinta qulqulka | Ka sarreeya cabbiraadda cabbirka shaqada buuxdhaafka ah: "OL" muujinta astaanta |
Imtixaanka Faragelinta | Aqoonso calaamadda faragelinta si toos ah, wdigaagdanab faragelindhaafo5V,waxaa jira "Buuq” tilmaanta digniinta |
Imtixaanka dhulka caawinta | 0.00KΩ-30kΩ(100R+rC<50kΩ, 100R+rP <50kΩ) |
Shaqada alaarmiga | Marka la cabbirayo qiimaha uu dhaafo qiimaha dejinta alaarmiga, waxaa jiradhawaaqqaylo-dhaan |
Voltage Battery | Marka danab batarigu hoos u dhaco ilaa 7.5V, icon danab yar oo batari ah" ayaa soo muuqan doona, xusuusin doonalacag |
Isticmaalka Korontada | heeganku saabsan20mA (Iftiinka dambe waa dansan yahay) |
Iftiin danbe: qiyaastii 45mA(Lalka dambe wuxuu damiyay 25mA) | |
Cabbirka: ilaa 100mA (Iftiinka dambe waa dansan yahay) | |
Miisaanka | Wadarta miisaanka boorsada: 4.5kg |
Tijaabiye: 950g (oo ay ku jiraan batari) | |
Tijaabada Xadhkaha: 1560g | |
Usha dhoobada caawisa: 935g (4PCS) | |
Heerkulka shaqada & qoyaanka | -10℃-40℃, ka hooseeya 80% rh |
Heerkulka kaydinta & qoyaanka | -20℃-60℃, ka hooseeya 70% rh |
Ilaalinta culayska badan | Cabbiraadda iska caabinta dhulka: inta u dhaxaysa is-dhexyaal kasta ooC (H)-E,P(S)-ES, AC 280V/3 ilbiriqsi |
Iska caabinta dahaarka | Dhamaaday20MΩ (inta u dhaxaysa wareegga iyo xayndaabku waa 500V) |
U adkaysiga Voltage | AC 3700V/rms (inta u dhaxaysa wareegga iyo xidhitaanka) |
Tilmaamaha Electromagnetic | IEC61326 (EMC) |
Nooca Ilaalinta | IEC61010-1 (CATIII 300V, CAT IV 150V, shahaadada wasakhowga2); IEC61010-031; IEC61557-1Iska caabinta Dhulka); IEC61557-5Iska caabbinta ciidda); JJG 366-2004 |
3. Khaladka aasaasiga ah iyo waxqabadka hoos yimaada xaaladda caadiga ah
Walxaha | Qiyaasta kala duwan | Saxnaanta | Qaraarka |
Iska caabinta dhulka (R) | 0.00Ω~30.00Ω | ±2%rdg±3dgt | 0.01Ω |
30.0Ω~300.0Ω | ±2%rdg±3dgt | 0.1Ω | |
300Ω~3000Ω | ±2%rdg±3dgt | 1Ω | |
3.00kΩ~30.00kΩ | ± 4%rdg 3dgt | 10Ω | |
Iska caabbinta ciidda (ρ) | 0.00Ωm~99.99Ωm | Marka loo eego saxnaanta R(ρ=2πaR ah:1 m-100m; π=3.14) | 0.01Ωm |
100.0Ωm~999.9Ωm | 0.1Ωm | ||
1000Ωm~9999Ωm | 1Ωm | ||
10.00kΩm~99.99kΩm | 10Ωm | ||
100.0kΩm~999.9kΩm | 100Ωm | ||
1000kΩm~9000kΩm | 1kΩm | ||
danab dhulka | AC 0.0~600V | ±2% rdg±3dgt | 0.1V |
Odhaah:1. qalad dheeraad ah: ≤± 3%rdg±5dgt hoos rC max ama rP max.(rC ugu badnaan: 4kΩ+100R<50kΩ, rP max: 4kΩ+100R<50kΩ)
2. qalad dheeraad ah: ≤ ± 5% rdg ± 5dgt hoos 5V danab faragelinta